PANEL MODEL     

VENT-AXIA \\\  DIRECT DRIVE PANEL FANS

 
 

OVERVIEW
 
Vent-Axia direct drive axial panel fans are based on an integrated impeller and internal rotor motor design which produces a very compact unit. Together with a specially designed bellmouth inlet and mounting plate, the complete fan is both lightweight and ensures an excellent performance to sound level ratio. The mounting plate is formed from sheet metal protected with an industrial epoxy finish.
 

FEATURES
 
IMPELLERS
Moulded in glass filled polyamide for resistance to outdoor conditions and abrasive airflow.
 
AXIAL MOTORS
The internal rotor motors are purpose designed and styled for this range of fans. Ball bearings are greased for life and allow the fans to be installed at any angle. Motors are protected against dust and water-jets. They have ribbed aluminum body castings for efficient cooling. Motor insulation is Class ‘F’ (from -40°F to 155°F).
 
ELECTRICAL
Single phase 120V 60Hz. Capacitor start and run. A terminal box is supplied with all models. All motors are fitted with Standard Thermal Overload Protection (S.T.O.P).
 
TERMINAL BOX
Protected against dust and water jets from any angle allowing outside applications.
  

ACCESSORIES
 
LOUVER SHUTTER
 
A range of five sizes for wall mounting. Square opening behind a square frame for maximum free area. The frame is manufactured from high impact polystyrene and the louvers from P.V.C.
All components are UV stabilized. Colour: Light gray.
 
  

TYPICAL INSTALLATION

  

DIMENSIONS


Nominal
blade Ø
b
c
e
g
lb
in
in
in
in
in
in
in
in
in
12
13
5 1/16
15 3/4
12 7/16
1 7/8
3/8
2 7/8
12 15/16
15
16
16 9/16
5 1/16
19 11/16
15 3/4
1 5/8
3/8
3 1/16
16 5/8
20
18
18 15/16
5 7/8
22 1/16
17 3/4
1 7/8
3/8
3 13/16
18 3/4
29
20
21 1/16
5 7/8
24 13/16
19 11/16
1 3/4
3/8
3 13/16
21 1/8
34
 
 
Model
Input
Watt
Peak
BHP
rpm
C.F.M. @ In. w.g.
Sones
0
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.50
p12/1/4
132
-
1500
1260
1200
1130
1040
900
-
-
-
-
-
9.9
P16/1/4
310
0.26
1500
2430
2350
2260
2160
2050
1840
1500
-
-
-
18.9
P18/1/4
550
0.50
1465
3690
3600
3510
3410
3330
3240
3140
3020
2900
2500
19.7
P20/1/4
750
0.65
1500
4520
4440
4340
4220
4100
3990
3870
3740
3600
3160
28
Speed (rpm) shown is nominal. Performance is based on actual speed of test. Performance ratings include the effects of finger guards in the airstream. The sound ratings are loudness values in fan sones at 5ft in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet fan sone levels. Performance shown is for Installation Type A: free inlet, free outlet.

DIRECT DRIVE AXIAL FANS